手机版
1 2 3 4
首页 > 新闻中心 > 翻译公司资讯 >
翻译公司资讯

世联翻译公司完成“流体设备”英文翻译

发布时间:2020-01-09 08:57  点击:

世联翻译公司完成“流体设备”英文翻译
    Exhaust
Base engine Speed backpressure limit
All JU4   30
All JU6 except models below   30
UF34, UF54, UFAB76, UF84 2800 25
UF34, UF54, UF84 3000 25
UF30, UFG8,    
UFABL8, UFM8, UF58, 1470 20
UF68, UFAAPG    
 
 
148
Note: Intake Air Shutoff Valve - Engine may include an intake air shutoff valve as an optional feature that is activated by an overspeed event and provides a positive shutoff of combustion air to the engine. The optional air intake shutoff valve has not been evaluated by UL as part of a UL Listed fire pump driver.
 
 
147
Base engine Speed Air filter restriction
All JU4   10
All JU6 except models below   12
UF30, UFABL8, UFM8, UF58, UF68, UFAAPG 1470 10
UFD0, UFD2, UF30, UF32, UFABL0, UFABL2, UFM0, UFM2, UF50, UF52, UF60, UF62 2350 13
UFD2, UF32, UFABL2, UFM2, UF52, UF62 2600 13
 
 
159
 
3.5.5 Mechanical Engine Control and Alarm Board (MECAB) Speed Switch Troubleshooting
This engine may be equipped with a speed switch p/n C071571 capable of sensing engine sensor malfunctions and/or electrical over-current(s) on engine alarm circuits and alerting the user via flashing status lamps. This flashing status indication is done so with the red “OVERSPEED SHUTDOWN” lamp on the outside of the Clarke instrument panel (Figure #37A) and a red LED located on the middle of the speed switch inside of the Clarke instrument panel (Figure #37B). In addition to these flashing status lamps, a “Low Engine Coolant Temperature Alarm” is sent via engine / fire pump controller inter-connect circuit #312 as a means to alert the user outside of the engine room.
Note: When first applying battery power to the engine, or after activating the overspeed reset switch, the OVERSPEED SHUTDOWN lamp and red LED on the speed switch will flash several times. This is an “INITIALIZATION PATTERN” and is normal.
This will be referred to in the following troubleshooting section.
 
Figure #37A
List of Troubleshooting Malfunctions
Two (2) blinks – Electrical Current Exceeds 10 Amps on Alarm Circuits: Status lamps will flash two times continuously on the Clarke instrument panel and a “Low Engine Coolant Temperature” alarm will be sent to the fire pump controller via circuit #312.
Cause:
Electrical current exceeds 10 amps on one or more engine / fire pump controller inter-connect circuits
Engine run alarm (#2)
Engine overspeed alarm (#3)
Engine low oil pressure alarm (#4)
Engine high coolant temperature alarm (#5)
Engine low coolant temperature alarm (#312)
 
Corrective actions:
Check each of the above circuits to determine which contains the current overload.
Once circuit(s) overload are corrected: On the Clarke instrument panel, operate the “OVERSPEED RESET” switch for two (2) seconds and release (Figure #37C).
 
The “INITIALIZATION PATTERN will flash. This is normal. The continuous two (2) blink flash sequence should turn off at this point.
Three (3) blinks – Engine Coolant Temperature Sensor malfunction: Status lamps will flash three times continuously on the Clarke instrument panel and a “Low Engine Coolant Temperature” alarm will be sent to the fire pump controller via circuit #312.
 
Cause:
Engine coolant temperature sensor circuit is open or closed
Corrective Actions:
Verify wiring and connector plug at engine coolant temperature sensor are secure. Sensor is located behind engine thermostat housing
 
On the Clarke instrument panel, operate the “OVERSPEED RESET” switch for two (2) seconds and release. (Refer to Figure #37C).
The “INITIALIZATION PATTERN will flash. This is normal. The continuous three (3) blink flash sequence should turn off at this point.
 
If problem still exists, replace engine coolant temperature sensor, Clarke part number C071607
Five (5) blinks on instrument panel – Oil pressure switch or Engine speed sensor (magnetic pick-up) malfunction: Status lamps will flash five times continuously on the Clarke instrument panel and a “Low Engine Coolant Temperature” alarm will be sent to the fire pump controller via circuit #312.
Cause:
Oil pressure switch failure or magnetic pick-up failure.
 
Corrective Actions:
Oil Pressure switch check
Verify wiring and connector at engine oil pressure switch are secure. Pressure switch is located on left side of engine (JU models) and right side of engine (JW models)
With engine off, check continuity between the two terminals on the oil pressure switch. Note, do not disconnect wires when performing this task.
 
If circuit is open, replace oil pressure switch, Clarke part number C072011.
After new switch is replaced: On the Clarke instrument panel, operate the “OVERSPEED RESET” switch for two (2) seconds and release.
(Refer to Figure #37C)
The “INITIALIZATION PATTERN will flash. This is normal. The continuous five (5) blink flash sequence should turn off at this point.
 
If circuit is closed, the oil pressure switch is not damaged and is working normally as expected. Proceed to engine speed sensor check, below. Engine speed sensor (magnetic pick-up) check Verify wiring and connector at engine speed sensor are secure. Magnetic pick-up is located on top of the flywheel housing.
 
With engine running, verify that the tachometer is functioning normally.
Refer to section 3.5.4 of Engine Operator’s Manual to properly reposition the magnetic pick-up if tachometer is not functioning.
Once magnetic pick-up is repositioned: On the Clarke instrument panel, operate the “OVERSPEED RESET” switch for two (2) seconds and release.
(Refer to Figure #37C).
 
“OVERSPEED SHUTDOWN” lamp will flash a sequence of one (1) blink, then four (4) blinks. This is normal. The continuous five (5) blink flash sequence should turn off at this point. If problem still exists, replace engine speed sensor (magnetic pickup), Clarke part number C071883.
 
3.5.6 FIELD SIMULATION OF PUMP CONTROLLER ALARMS
Field simulation of (5) pump controller alarms
• Alarm 1: Over speed Shutdown: Follow over speed verification steps per section 3.5.3.
• Alarm 2: Low Oil Pressure: With the engine running, jumper across two outer terminals with wires attached to the engine mounted Low Oil Pressure switch.
Wait for 15 seconds and controller alarm will activate.
• Alarm 3: High Engine Coolant Temperature: With the engine running, set the High Engine Coolant Temperature DIP switch to “ON” (see Figure #37D). Use a fine pick or small screwdriver and slide the white slider to the left. Wait for 30 seconds and controller alarm will activate. Set white DIP switch slider to “OFF” (right) when simulation is complete.
 
Low Coolant Temperature Simulation switch
High Coolant Temperature Simulation switch
OFF
ON
Figure #37D
• Alarm 5: Overcrank: NEVER shut off the fuel supply to the engine to prevent it from starting. Shutting off the fuel supply will cause an air lock condition in the fuel system and possibly cause fuel system component damage.
ETR Governor Solenoid: Activate and hold the Overspeed Reset switch while performing the overcrank test. Switch must be held continuously each time the engine attempts a crank start. This will allow the engine to crank only but will prevent it from running.
ETS Governor Solenoid: Use manual stop override to prevent the engine from starting during the cycle-crank testing. Override must be held continuously each time the engine attempts a crank start. This will allow the engine to crank only but will prevent it from running.
 
154
3.4.7.1 Raw Water Supply
Most Clarke diesel engine fire pump drivers are heat exchanger cooled and some engines also have a charge air cooler (CAC) that uses raw water to cool the air before entering the intake manifold. If you have a radiator cooled Clarke engine, you can disregard this section. Heat exchanger cooled diesel engine drivers require a clean source of pressurized water from the discharge side of the fire pump in order to keep the engine from overheating by providing a specified minimum amount of raw water flow.
3.4.7.2 Cooling Loop
Note: Engine may include a cooling loop as an optional feature and has not been evaluated by UL as part of a UL Listed fire pump driver.
Figure #35D shows the standard NFPA 20 cooling loop piping arrangement. The cooling loop consists of an Automatic flow line with a 12V or 24V solenoid valve (HSC and ES pump applications only) that is energized to open anytime the engine is called upon to run from either the fire pump controller or from the engine instrument panel.
NOTE: VT type pumps applications do not require a solenoid valve in the Automatic flow line.
NOTE: With the Mechanical Engine and Alarm Control Board, See section 3.5.5, the solenoid valve will open 15 seconds after engine shutdown and will stay open for 60 seconds. This allows for raw water to flow through the heat exchanger and reduce the heat soak rise caused in the engine.
The second flow line is called the Manual by-pass line and it can be opened at any time if for any reason the engine shows signs of overheating. Each line has two (quarter turn) shutoff values installed and the normal position of the shutoff valve is to remain open in the Automatic flow line and remain closed in the Manual by-pass flow line.
NOTE: Opening up both lines to flow is never a problem should there be some concern of engine overheat, especially if there is an emergency situation. The Manual by-pass line can only be opened by an operator in the pump room.
The shutoff valves are all identified to show which are Normally Open (Automatic flow line) and which are Normally Closed (Manual by-pass flow line).
The shutoff valves are also used to isolate water pressure in the event of maintenance to pressure regulators, strainers and solenoid valve. Shutoff valves in the automatic flow line are provided with lockable handles for cooling loops that have been tested to FM requirements.
In each flow line there is also a pressure regulator. Each pressure regulator protects the downstream piping from over-pressurization which includes the tube side of the engine shell & tube heat exchanger (or CAC) and to control raw water flow rate. Typically the pressure regulators are set to limit downstream pressure to 60 psi (4 bar). There is a pressure gauge installed just upstream of the engine heat exchanger (or CAC) and downstream of the each pressure regulator. Under normal engine operating conditions with adequate cooling water flowing thru the heat exchanger (or CAC) this gauge should typically read below 20 psi (1.4 Bar).
Strainers are used to remove debris from the raw water supply. One strainer is in the Automatic flow line and the other is in the Manual by-pass flow line.
Note: See section 3.4.7.5 regarding strainer maintenance.

Standard Cooling Loop
Figure #35D
3.4.7.3 Setting Raw Water Flow Rate
The proper amount of raw water flow thru this line is of the utmost importance, and the pressure gauge value does little to indicate if there is sufficient flow. When the engine is exercised weekly, the amount of raw water flow exiting the piping to a floor drain should always be checked to verify it does not appear to have diminished.
During initial commissioning of the engine, it is important to correctly set the raw flow rate going thru the cooling loop. Each Clarke engine model has an Installation and Operation (I&O) Datasheet that provides basic operating conditions of the engine and most values are given based upon engine speed. You will find this datasheet in the Technical Catalog that is shipped with the engine for your specific Clarke model. This datasheet must be available during commissioning in order to set the proper minimum raw water flow. You will need to measure the raw water temperature and then find the value for recommended minimum raw water flow at your measured raw water temperature on the I&O Datasheet and then; with the fire pump flowing 150% of rated flow, and the Automatic flow line open; set minimum flow by using the adjusting screw at the top of the pressure regulator.
NOTE: To increase flow turn the adjusting screw clockwise and to reduce flow turn the adjusting screw counterclockwise.
You will need to capture the flow for a specific amount of time coming out of the heat exchanger and going to a floor drain in order to establish a reasonably accurate flow rate value. Using a container or bucket of known volume, record the time required to fill the container and compare to the gpm or L/min value provided on the I&O datasheet.
THIS IS CRITICAL FOR PROPER ENGINE COOLING AT MAXIMUM PUMP LOAD! After setting the pressure regulator in the Automatic flowline, open the Manual by-pass line valves, and then close the Automatic flowline valves and repeat the above process in order to set the flowrate going thru the pressure regulator in the Manual by-pass line. Once this is completed; close the Manual bypass valves and open the Automatic flowline valves to restore conditions back to normal.
3.4.7.4 Raw Water Outlet
NOTE: NFPA 20 does allow for the heat exchanger outlet flow to be returned to a suction reservoir. This makes it very difficult to measure the flowrate. When discharging to a suction reservoir, NFPA provides additional requirements:
1) A visual flow indicator and temperature indicator are installed in the discharge (waste outlet) piping.
2) When waste outlet piping is longer than 15ft (4.6m) and / or the outlet discharges are more
than 4ft (1.2M) higher than the heat exchanger, the pipe size increased by at least one size.
3) Verify that when the correct flow rate is achieved that the inlet pressure to the heat exchanger (or CAC) does not exceed 60psi (4bar)
If you have such an installation, it is recommended that you run the engine for a period of time at firepump 150% flow and confirm the visual flow indicator is showing water flow, the temperature rise is not excessive (usually no more than 40F (4.5C) over ambient raw water temperature) and the engine is showing no signs of overheating.
3.4.7.5 Raw Water Quality, Strainers and Deterioration of Heat Exchanger (or CAC)
Over time, as the heat exchanger (or CAC) begins to plug and foul, this pressure will rise and the flow will diminish which could mean that the heat exchanger (or CAC) may have to be replaced.
It can be not stressed enough how important it is to keep these strainers clean: Most engine failures occur due to plugged cooling loop strainers! If the raw water supply has debris in it (leaves, stones, etc) as the strainer accumulates more debris (that will not pass thru it), the flowrate will continue to diminish which will eventually starve the engine of adequate cooling water flow which will lead to engine overheat and catastrophic engine failure. When this occurs you have no fire protection! Clarke recommends that after the initial engine commissioning and also prior to each weekly exercise of the engine / fire pump set, both strainers be removed and cleaned and then re-installed before starting the engine.
3.4.7.6 Backflow Preventers
NFPA20 allows for the use of backflow preventers in the Automatic and Manual flow line of the cooling loop as required by local code. For specific application information contact factory.
3.4.7.7 Raw Water Outlet Temperature
Certain local codes may not allow you to discharge the waste water outlet from the engine heat exchanger either due to its temperature or it now being considered hazardous waste. It is
recommended you always check local codes regarding waste water discharge.
3.4.8 Flow Paths of Engine Cooling System
The engine coolant flows through the shell side of the heat exchanger (or radiator), engine coolant pump, oil cooler, engine block and cylinder head, jacket water heater, thermostat, expansion tank, and coolant recovery tank (if equipped).
On heat exchanger equipped engines raw cooling water flows through the tube side of the charge air cooler, if equipped, and the tube side of the heat exchanger.
Refer to Figures #35E for heat exchanger cooled engines and #35F for radiator cooled engines for cooling system flow path diagrams.
 
Figure 35F- radiator cooled engines
3.4.9 IMPORTANT SERVICE NOTICE
Any time an engine experiences a high coolant temperature alarm condition the primary cause of the overheat must be determined and the cause corrected to prevent a recurring overheat event.. Additionally, if an event of a restricted flow, collapsed hose, insufficient coolant level or failed pressure cap is experienced, further investigation of the cooling system is required.
 
1) The coolant shoud be drained (after deenergizing the coolant heater
2) Replace the engine thermostat(s)
3) Remove the engine water pump and inspect the impeller and seal for damage, replace as necessary. Reassemble and refill coolant according to the Installation and Operations Instruction Manual.
4) Run the engine to verify normal operating temperature.
3.4.9.1 Water Pump Cavitation
Cavitation is a condition that occurs when bubbles form in the coolant flow in the low pressure areas of the cooling system and implode as they pass to the higher pressure areas of the system. This can result in damage to cooling system components, particularly the water pump impeller and cylinder liners.
Cavitation in an engine can be caused by:
 Improper coolant
 Restricted coolant flow caused by collapsed hose or plugged system
 Coolant fill cap is loose or unable to retain the required pressure
 Insufficient fluid level
 Failure to de-aerate
 Overheat
151
3.4.1 Intended Engine Operating Temperature
The JU and JW engines are provided with either a heat exchanger or radiator to maintain the engine coolant temperature within recommended operating guidelines.
The JU4H, JU6H, and JW6H have an intended engine operating temperature of 160º F (71ºC) to 185º F (85º C). A high coolant temperature switch is provided to indicate a high coolant temperature alarm at 205º F (96º C) for heat exchanger cooled models and 215°F (102° C) for radiator cooled models.
 
2.6.4 Emergency Operation – ETR Engines Only
UL/FM Energized To Run (ETR) engines only In the event that the speed switch fails to energize the engine’s fuel injection pump solenoid, the engine instrument panel has been equipped with an Emergency Run Switch. This switch sends battery voltage directly to the fuel injection pump solenoid which allows for operation of the engine.
Additionally, the Emergency Run Switch will activate the engine raw water cooling loop solenoid if the engine is equipped with one.
If engine fails to run with standard starting procedures, follow these steps to start engine with Emergency Run Switch:
1. Open the door of the instrument panel
2. Locate the Emergency Run Switch, denoted by the yellow indication label
3. Remove the lock-out screw
4. Toggle switch to the ON position
a. Battery voltage will be sent to the fuel injection pump solenoid and the raw water cooling loop solenoid
5. To shut engine down ensure engine mode selector switch is set to Auto/Manual Stop, fire pump controller is keyed to OFF, and toggle the engine Emergency Run Switch to OFF position.
Note, activating the Emergency Run Switch will energize the fuel solenoid and the raw water cooling loop solenoid until the switch is returned to the OFF position. The switch should only be used as a manual, emergency means for operation of the engine in the event of speed switch failure. Replace speed switch immediately upon finding failure.
  
UL/FM Front Opening Instrument Panel
1 Emergency Operating Instructions
2 Automatic-Manual Mode Selector
Manual Crank Controls
4 Overspeed Reset
5 Manual Mode Warning Light
Overspeed Verification
Overspeed Indication Light
 
120
Turn off all cooling water lines.
109
Test for parallel and angular alignment with a straight edge and feeler gauge as shown in manufacturer’s instructions (at the end of this section). With coupling halves stationary, make trials at four places 90º apart. Perfect alignment occurs when a straight edge is level across the coupling halves and the same gauge just enters between the halves, both conditions at all points.
 
37
b) Air temperature

Unitrans世联翻译公司在您身边,离您近的翻译公司,心贴心的专业服务,专业的全球语言翻译与信息解决方案供应商,专业翻译机构品牌。无论在本地,国内还是海外,我们的专业、星级体贴服务,为您的事业加速!世联翻译公司在北京、上海、深圳等国际交往城市设有翻译基地,业务覆盖全国城市。每天有近百万字节的信息和贸易通过世联走向全球!积累了大量政商用户数据,翻译人才库数据,多语种语料库大数据。世联品牌和服务品质已得到政务防务和国际组织、跨国公司和大中型企业等近万用户的认可。 专业翻译公司,北京翻译公司,上海翻译公司,英文翻译,日文翻译,韩语翻译,翻译公司排行榜,翻译公司收费价格表,翻译公司收费标准,翻译公司北京,翻译公司上海。
  • “贵司提交的稿件专业词汇用词准确,语言表达流畅,排版规范, 且服务态度好。在贵司的帮助下,我司的编制周期得以缩短,稿件语言的表达质量得到很大提升”

    华东建筑设计研究总院

  • “我单位是一家总部位于丹麦的高科技企业,和世联翻译第一次接触,心中仍有着一定的犹豫,贵司专业的译员与高水准的服务,得到了国外合作伙伴的认可!”

    世万保制动器(上海)有限公司

  • “我公司是一家荷兰驻华分公司,主要致力于行为学研究软件、仪器和集成系统的开发和销售工作,所需翻译的英文说明书专业性强,翻译难度较大,贵司总能提供优质的服务。”

    诺达思(北京)信息技术有限责任公司

  • “为我司在东南亚地区的业务开拓提供小语种翻译服务中,翻译稿件格式美观整洁,能最大程度的还原原文的样式,同时翻译质量和速度也得到我司的肯定和好评!”

    上海大众

  • “在此之前,我们公司和其他翻译公司有过合作,但是翻译质量实在不敢恭维,所以当我认识刘颖洁以后,对她的专业性和贵公司翻译的质量非常满意,随即签署了长期合作合同。”

    银泰资源股份有限公司

  • “我行自2017年与世联翻译合作,合作过程中十分愉快。特别感谢Jasmine Liu, 态度热情亲切,有耐心,对我行提出的要求落实到位,体现了非常高的专业性。”

    南洋商业银行

  • “与我公司对接的世联翻译客服经理,可以及时对我们的要求进行反馈,也会尽量满足我们临时紧急的文件翻译要求。热情周到的服务给我们留下深刻印象!”

    黑龙江飞鹤乳业有限公司

  • “翻译金融行业文件各式各样版式复杂,试译多家翻译公司,后经过比价、比服务、比质量等流程下来,最终敲定了世联翻译。非常感谢你们提供的优质服务。”

    国金证券股份有限公司

  • “我司所需翻译的资料专业性强,涉及面广,翻译难度大,贵司总能提供优质的服务。在一次业主单位对完工资料质量的抽查中,我司因为俄文翻译质量过关而受到了好评。”

    中辰汇通科技有限责任公司

  • “我司在2014年与贵公司建立合作关系,贵公司的翻译服务质量高、速度快、态度好,赢得了我司各部门的一致好评。贵司经理工作认真踏实,特此致以诚挚的感谢!”

    新华联国际置地(马来西亚)有限公司

  • “我们需要的翻译人员,不论是笔译还是口译,都需要具有很强的专业性,贵公司的德文翻译稿件和现场的同声传译都得到了我公司和合作伙伴的充分肯定。”

    西马远东医疗投资管理有限公司

  • “在这5年中,世联翻译公司人员对工作的认真、负责、热情、周到深深的打动了我。不仅译件质量好,交稿时间及时,还能在我司资金周转紧张时给予体谅。”

    华润万东医疗装备股份有限公司

  • “我公司与世联翻译一直保持着长期合作关系,这家公司报价合理,质量可靠,效率又高。他们翻译的译文发到国外公司,对方也很认可。”

    北京世博达科技发展有限公司

  • “贵公司翻译的译文质量很高,语言表达流畅、排版格式规范、专业术语翻译到位、翻译的速度非常快、后期服务热情。我司翻译了大量的专业文件,经过长久合作,名副其实,值得信赖。”

    北京塞特雷特科技有限公司

  • “针对我们农业科研论文写作要求,尽量寻找专业对口的专家为我提供翻译服务,最后又按照学术期刊的要求,提供润色原稿和相关的证明文件。非常感谢世联翻译公司!”

    中国农科院

  • “世联的客服经理态度热情亲切,对我们提出的要求都落实到位,回答我们的问题也非常有耐心。译员十分专业,工作尽职尽责,获得与其共事的公司总部同事们的一致高度认可。”

    格莱姆公司

  • “我公司与马来西亚政府有相关业务往来,急需翻译项目报备材料。在经过对各个翻译公司的服务水平和质量的权衡下,我们选择了世联翻译公司。翻译很成功,公司领导非常满意。”

    北京韬盛科技发展有限公司

  • “客服经理能一贯热情负责的完成每一次翻译工作的组织及沟通。为客户与译员之间搭起顺畅的沟通桥梁。能协助我方建立专业词库,并向译员准确传达落实,准确及高效的完成统一风格。”

    HEURTEY PETROCHEM法国赫锑石化

  • “贵公司与我社对翻译项目进行了几次详细的会谈,期间公司负责人和廖小姐还亲自来我社拜访,对待工作热情,专业度高,我们双方达成了很好的共识。对贵公司的服务给予好评!”

    东华大学出版社

  • “非常感谢世联翻译!我们对此次缅甸语访谈翻译项目非常满意,世联在充分了解我司项目的翻译意图情况下,即高效又保质地完成了译文。”

    上海奥美广告有限公司

  • “在合作过程中,世联翻译保质、保量、及时的完成我们交给的翻译工作。客户经理工作积极,服务热情、周到,能全面的了解客户的需求,在此表示特别的感谢。”

    北京中唐电工程咨询有限公司

  • “我们通过图书翻译项目与你们相识乃至建立友谊,你们报价合理、服务细致、翻译质量可靠。请允许我们借此机会向你们表示衷心的感谢!”

    山东教育出版社

  • “很满意世联的翻译质量,交稿准时,中英互译都比较好,措辞和句式结构都比较地道,译文忠实于原文。TNC是一家国际环保组织,发给我们美国总部的同事后,他们反应也不错。”

    TNC大自然保护协会

  • “原英国首相布莱尔来访,需要非常专业的同声传译服务,因是第一次接触,心中仍有着一定的犹豫,但是贵司专业的译员与高水准的服务,给我们留下了非常深刻的印象。”

    北京师范大学壹基金公益研究院

  • “在与世联翻译合作期间,世联秉承着“上善若水、厚德载物”的文化理念,以上乘的品质和质量,信守对客户的承诺,出色地完成了我公司交予的翻译工作。”

    国科创新(北京)信息咨询中心

  • “由于项目要求时间相当紧凑,所以世联在保证质量的前提下,尽力按照时间完成任务。使我们在世博会俄罗斯馆日活动中准备充足,并受到一致好评。”

    北京华国之窗咨询有限公司

  • “贵公司针对客户需要,挑选优秀的译员承接项目,翻译过程客户随时查看中途稿,并且与客户沟通术语方面的知识,能够更准确的了解到客户的需求,确保稿件高质量。”

    日工建机(北京)国际进出口有限公司

15811068017

15801211926

18801485229
点击添加微信

无需转接等回电